Regulation 66, 67, 68
Monthly Inspection · 每月检查
Source: st.gov.my/en/details/policies_details/7/2 ↗电压不超过 600V,且通过额定 100A 或以上的开关设备供电的装置
Inspection and Test for the Purpose of Maintenance of Installation
Installation
An installation, other than a domestic installation, shall be checked and tested by a competent person at least once in every five years, or at any time as directed by the Commission.
非住宅类电气装置须至少每 5 年由合格人员检查与测试一次,或按能源委员会指示执行。
Protective Relay & Device
Any protective relay and device of an installation shall be checked, tested and calibrated by a competent person at least once in every two years, or at any time as directed by the Commission.
所有保护继电器与保护装置须至少每 2 年检查、测试及校准一次,或按能源委员会指示执行。
Proposed Routine Test on Electrical Installation
| Routine Test | Frequency |
|---|---|
| Monthly InspectionAs stated in Regulation 66, 67, 68 · 每月检查 | Monthly |
| Protection Relay CalibrationEvery two years as regulations · 保护继电器校准 | Every 2 Years |
| Maintenance Service of EquipmentTo check all mechanism and condition (Regulation is stated 5 years) · 设备维护服务 | Every 2 Years |
| Oil Sampling (if applicable)油样检测(如适用) | Annually |
| Infrared Thermography Scanning and Partial Discharge Scanning红外热成像与局部放电扫描 | Annually |
| Earthing (Electrical and Lightning Protection)接地系统(电气及防雷) | Annually |
| Earth Loop TestingWhile doing calibration · 接地回路测试 | Every 2 Years |
| Capacitor Bank CheckingWhile doing calibration · 电容器组检查 | Every 2 Years |
No person shall perform or carry out any maintenance and repair, overhaul and service, test and commission of any installation or equipment and location of cable faults unless he holds a valid Certificate of Registration as an Electrical Services Contractor issued under these regulations.
任何人若未持有由法规颁发的有效电气服务承包商注册证书,不得进行任何维护、维修、检修、测试、调试或电缆故障定位工作。
View Our Registration